Specialists in Measurement, Control and Alarm Systems
 
Specifications - 1200 Data Logger
 
Product
Information

 
1200 Data Logger Data Sheet
INPUTS 8 to 32 Differential Inputs - standard ranges include 20mV, 200mV, 2V, 4-20mA, J, K, T, R, and N thermocouples. Users can also custom calibrate almost any non standard sensor.
RANGE Standard Calibrations - : Full range for standard calibrations up to ±30K. Typically full range for custom sensors. Please enquire for details.
RESOLUTION Input Resolution - Up to 1 part in 32768 – 16bit (max).
ACCURACY Sensor/Application Dependent - Please enquire for details (±2 LSB).
COLD JUNCTION Optional For temperature Measurement - NTC 10K 0.1 resolution with standard accuracy of ±0.3 degrees C.
EXITATION Factory Configured - Typically 5 or 10V DC at 100mA per channel used for load cells,pressure transducers etc.
DISPLAY LCD - Backlit 4 x 20 LCD as standard.
LOGGING INTERVAL Selectable - Selectable Linear, Log and Square root timebases. Linear timebase settings from 6 seconds to 12 hours in 1 second increments. Each channel has an independent timebase.
MEMORY Storage - 16,000 readings held in non-volatile memory. Optional additional capacity's available.
CLOCK Internal Realtime Clock - Battery backed to date and time stamp all logged data.
COMMUNICATION

Standard RS232 and USB - Standard RS232 and USB for computer connection.
Optional network interface with standard RJ45 connector.
Optional RS485 interface.

Optional wireless Bluetooth Interface.

CONVERSION 16 Bit A/D Converter - 16 bits for range and accuracy.
CONNECTIONS Factory Configured - Customer specified connections to suit the sensor requirements.
POWER Mains - 115V/230V 50/60Hz @ 30VA approx.
DIMENSIONS

Size - 120mm by 350mm by 263mm(8-16 ch.)
150mm by 350mm by 263mm (17-32 ch.)

WEIGHT Nominal - 3KG.
SOFTWARE Windows - Communication and data logging software suitable for Windows 98SE, Me, 2000 and XP supplied as standard. Custom packages available.
ENVIRONMENT Operating - 0 to 50 Degrees C, 5 to 90% relative humidity non condensing.
STORAGE Environment - -20 to +70 degrees C and 5 to 90% humidity non condensing.